4.2 Basic calibration with a signal output from 0 ... 20 mA
1. Select the temperature range on the printed circuit board
using the DIP switch, see table on the module or pages 41
and 42.
The DIP switches 1, 2 and 3 set the minimum input tempera-
ture ϑ
min
.
The span (difference between minimum and maximum input
temperature) is set using the DIP switches 4, 5 and 6.
2. Professionally install module.
3. Add 1 % of the temperatur e span to the selected “ minimum”
temperature and set this value on a PT 100 simulator (when
using a pr ecision resistance decade, wher e necessary ob-
serve DIN IEC 751 conversion table fr om °C to Ω!) and cali-
brate the signal conditioner output signal to 0.200 mA using
the null potentiometer. (The potentiometers are located be-
hind the hinged cover).
4. Set the “ maximum” selected temperature on a PT 100 simu-
lator (or precision resistance decade) and calibrate the signal
output to 20.000 mA using the S pan potentiometer .
5. Repeat steps 3 and 4 (approx. 2-3 times), until the required
accuracy is achieved.