Bedienungsanleitung
Zweikanaliges
Grenzwertüberwachungsmodul 3
Operating instructions
Two-channel
threshold monitoring module 13
DPA/DMA 61001035/00/01.08
Vista de página 0
1 2 3 4 5 6 ... 23 24

Resumo do Conteúdo

Página 1 - DPA/DMA 61001035/00/01.08

deenBedienungsanleitungZweikanaliges Grenzwertüberwachungsmodul 3Operating instructionsTwo-channel threshold monitoring module 13DPA/DMA 61001035

Página 2

10Totbandeinstellung (Regler DB)Der Totbandregler dient zum Einstellen des Schaltpunktes, bei dem der ausgelöste Alarm zurückgesetzt werden soll. Bei

Página 3

11ModifizierungLinke Seitenwand entfernen1. Lösen Sie die sechs mit A-F markierten Schneidklemm-schrauben (zuvor Spannungs-versorgung unterbrechen).2.

Página 4 - • Betrieb

12DPA-Hauptplatine und Darstellung der Position für Modus ‘hoch’ bzw ‘niedrig’ sowie der Relaisspulenerregung und AuswahljumperBrücken für die Auswah

Página 5

13en DPA/DMAContentsOperation 14Installation 15Calibration and Setup 18Modifications 20

Página 6

14en DPA/DMA• OperationGeneralThe DPA/DMA allows you to set two independent trip points on a DC milliamp signal (typically 4-20 mA). The alarm outputs

Página 7

15Sensor power supplyA 24 V DC power supply output is available for loop powered transmitter inputs to the DPA. It can supply currents up to 25 mA. In

Página 8

16Alarm connectionsThe DPA has a high inbuilt immunity to noise spikes caused by switching inductive loads like solenoids or relay coils. However, it

Página 9

17Cable preparation and installationFor effective protection from electromagnetic noise, all signal cables must be shielded, or located on conductive

Página 10

18• Calibration and SetupGeneralThe SET (setpoint) and DB (deadband) adjustments control the setpoint and hysteresis for each alarm channel. Internal

Página 11 - Modifizierung

191. Adjust the SET control2. Set the deadband to maximum by turning the DB control fully clockwise.3. Trigger the alarm by setting the input signal

Página 13

20ModificationsRemoving the left hand side plate1. Remove the six self tapping screws marked A-F (disconnect power first).2. Remove the two countersu

Página 14 - • Operation

21DPA main boa rd showing the location s of th e high/low operation, andrelay coil energisation, selection jump ersRelay energisation selection jumper

Página 17

Weidmüller Interface GmbH & Co. KGPostfach 303032720 DetmoldKlingenbergstraße 1632758 DetmoldTel. +49 5231 14-0Fax +49 5231 14-20 83info@weidmuell

Página 18 - • Calibration and Setup

3de DPA/DMAInhaltsverzeichnisBetrieb 4Installation 6Kalibrierung und Konfiguration 9Modifizierung 11

Página 19

4de DPA/DMA• BetriebAllgemeinDas DPA/DMA bietet die Möglichkeit, zwei unabhängige Schaltpunkte innerhalb eines DC-Milliampere-Signalbereichs (normaler

Página 20 - Modifications

5SensorstromversorgungFür schleifengespeiste Sensoren steht ein 24 V DC-Stromversorgungs-ausgang zur Verfügung. Dieser stellt einen Strom von bis zu 2

Página 21

6• InstallationAchtung: Zur Einhaltung der Produktsicherheitsanforderungen darf die Installation dieser Geräte nur von speziell ausgebildetem Fachpers

Página 22

7DPA/DMA1 22-Draht-Transmitter+–Verdrilltes ZweidrahtkabelKabelschirm nur auf Transmitterseite erdenDPA/DMA2 4DC mA-Quelle+–Verdrilltes Zweidrahtkabel

Página 23

8AnschlüsseKlemmeSignal1 24 V DC (Ausgang)Eingangssignale2 Signal +3 Nicht belegt4 Signal −5Nicht belegt6789 Neutral (−)Stromversorgung10 Phase (+)11

Página 24

9• Kalibrierung und KonfigurationAllgemeinDer Sollwert und die Hysterese der einzelnen Alarmkanäle werden über die Potentiometer SET (Sollwert) und DB