Status Output Setup
Status Output
sense
SOP1
Introduces Status Output One (AUTO/MAN) Setup - Next
A0n1
A1n0
Output ‘active’ when in automatic mode
Output ‘active’ when in manual mode
Toggle Accept
SOP2
Introduces Status Output Two (Handover) Setup - Next
HO=0
HO=1
Output ‘inactive’ when in handover mode
Output ‘active’ when in handover mode
Toggle Accept
Note: ‘active’ means switched to the Common/0V rail
Ca
libration options
Calibrate
Input?
C Pn
C Py
Skip input calibration
Calibrate inputs
Toggle Accept
Calibrate
Output?
COPn
COPy
Skip output calibration
Calibrate outputs
Toggle Accept
Password
PASS
Change Password? Change Skip
Save values
SAVE
Instrument is saving the changes to the setup and returning to normal
operation
During setup the Å and ì keys change values and toggle options.
The ENT key accepts changes and moves to the next item in the setup
sequence (see table for each installation configuration).
Do not use set-up mode if the instrument is in service.
Note: if you remove power during the setup sequence, any changes
you have made will not be saved.
I
n
strument Setup (continued)