Power Supply Requirements
Check the power supply against the model number before applying
p
ower to the instrument. DI350 displays must be used with a suitable
mains Power Supply, ratings are as follows:
Voltage Range Nominal Voltage Power Frequency
100–132 V AC 110 V AC 6 VA 47-63 Hz
200–264 V AC 240 V AC 6 VA 47-63 Hz
12–35 V DC* 24 V DC 4.5 W (at 24 V DC) -
*Using a DC power supply that provides this voltage will comply with
the instrument’s UL/CSA listing.
Connections
For effective protection from electromagnetic noise, all signal cables
must be shielded, or located on conductive trays or in conduits.
U
se 12-28 AWG Cu Wire rated for temperatures above 70 °C Only,
tighten to 4.5 lb-In. Strip wires to 7 mm from the ends. Use a suitable
ferrule for multistranded wires (do not solder).
Terminal Signal
1 +24 V DC
Sensor power supply (Output)
2 0V
3 S
ignal +
Analogue Input
4 Signal −
7 Live (+)
Power Supply
8 Neutral (−)